Heat Kit Photo Guide

Your electric heat kit has to match the breaker and wire that feed your indoor unit. Send a few photos and we’ll confirm the right kit — and the right matched set — before anything ships. This guide is for ducted heat pumps with an electric air handler. Mini splits do not use a heat kit.

The four photos that answer almost everything

  1. Outdoor unit data plate. The silver or white label on the side of the outdoor unit. The model number tells us the size (24 = 2 ton, 30 = 2.5, 36 = 3, 42 = 3.5, 48 = 4, 60 = 5).
  2. Indoor unit data plate. On the air handler in the closet, attic, or crawlspace. It shows the current heat kit and the electrical rating.
  3. Breaker panel, door open. We read the main breaker size and the breakers for the heat pump and air handler.
  4. The air handler breakers up close. The numbers on the handles (30, 40, 60) tell us which heat kits your wiring supports today.

Add a photo of the space around the indoor unit with a tape measure in view, and we can confirm the new air handler fits.

Start my photo review

Breaker & wire guide

Heat kitBreaker (240V)WireTypical system
5 kWOne 30A double-pole breaker#10 copper2 tons and under
8 kWOne 40A double-pole breaker#8 copperOptional on 2 tons and under
10 kWOne 60A double-pole breaker#6 copper2.5 – 3 tons (some northern 2-ton homes)
15 kWOne 60A + one 30A double-pole breaker (two circuits)#6 on the 60A, #10 on the 30A3.5 – 4 tons
20 kWTwo 60A double-pole breakers (two circuits)#6 copper on each5 tons

A general guide. Your unit’s nameplate (minimum circuit ampacity and max breaker), wire run, and local code decide the final answer, and we confirm it from your photos.

How to read what you have today

  • One 30A double-pole breaker on #10 wire: up to a 5 kW kit.
  • One 40A on #8: up to 8 kW.
  • One 60A on #6: up to 10 kW.
  • One 60A plus one 30A: 15 kW. The 15 kW kit runs on two circuits — the 60A on #6 wire and the 30A on #10.
  • Two 60A breakers, each on #6: 20 kW.

Why your main panel matters

Bigger heat kits draw a lot of power. On a 100A or 125A main panel, a 15 or 20 kW kit may not fit without electrical upgrades. Your main panel size, the wire already run, and the unit’s nameplate decide what can safely run.

What strip heat really costs to run

A heat kit is electric resistance heat, like a big space heater inside your air handler. It runs when the heat pump can’t keep up on the coldest days, often during defrost, and when you switch to emergency heat. Those are the hours your bill goes up the most, because strips use far more electricity for the same heat than the heat pump does. A bigger kit doesn’t make the system more efficient; it only adds backup heat for the coldest days. We size the kit for your home and wiring, not to make savings look bigger.

Electrical work not included. If your existing wiring or breaker isn’t adequate for the system or heat kit you purchase, the electrical work must be done by a qualified, licensed electrician. Those electrical costs are not included in Clear Price Air pricing.

This guide is general. The equipment nameplate (minimum circuit ampacity and maximum overcurrent protection) and local code decide the final answer. Don’t open a panel cover or touch wiring — a clear photo with the panel door open is all we need.